Secondary Racks

By :Taufiqullah Neutron (Masteropik)

Secondary racks usually support three spool insulators mounted
on a common shaft attached to a steel backing that is bolted to the
pole by one or more bolts (though sometimes, depending on the stress
to be accommodated, a lag screw may take the place of a bolt). The
spool insulators are usually spaced 8 in apart, although sometimes
less. If the rack is properly mounted, the insulators may fail before
the rack.

Loadings

The loading on secondary racks has both vertical and horizontal
components; see Figure 5-13. The vertical loading consists of the weight
of the conductors (with the coating of ice) of both the mains and services
attached to them.

With spool-type racks, the load is carried by small arms
acting as cantilever beams, supporting
the insulators. Generally, the insulator
is located between two such arms, but
only the lower one carries the load.
With the knob-type rack, the vertical
load is transmitted to the rear plate by
the U bolts attaching the insulators to
the plate, and to the pole by the bolts
attaching the rack to the pole.

The horizontal load is due to wind acting on ice-laden conductors
and the tension in them, for both the secondary mains and the services.
If the rack is attached to the pole by a bolt under each insulator, the
strength of the back plate plays little part, as the stress is transmitted
almost directly by the bolts.

Where the spool-type rack is mounted with
the bolts at the ends only (or by a bolt and a lag screw), the back of the
rack acts as a cantilever beam supported at both ends, with the load applied
at each of the points where the arms are attached to the back. The
greatest stress is at the point in the back where either of the two arms
supporting the middle insulator is attached, the bending moment being
greatest at that point. In the knob-type rack, both the vertical and horizontal
loadings are transmitted to the back of the rack and through the
mounting and bolts to the pole.

Where the conductors dead-end on a rack mounted on the side of
a pole (or where there is an unbalanced pull from broken conductors),
the side pull on the rack is limited by the strength of the arms or the U
bolts supporting the insulators. It is preferable to mount the rack on the
face of the pole, with the arms and U bolts supporting the insulators in
tension, and the stresses transmitted to the pole almost directly by the
mounting bolts.

In general, like pins, conductor fastenings should be able to withstand
a 700-lb stress.

Messenger Clamp

As mentioned earlier, when the secondary conductors are cabled
about the neutral conductor acting as the supporting messenger, a clamp
supporting the neutral is bolted to the pole. Here, both the vertical and
horizontal loadings are transmitted to the pole by the through bolt by
which the clamp is attached to the pole.
Read More - Secondary Racks

Pins

By :Taufiqullah Neutron (Masteropik)

Loading
Pins are subject to both vertical and horizontal loadings. The vertical
loading results from the weight of the conductor and its half-inch radial
coating of ice. The horizontal loading stems from the wind, from differential
tensions in adjacent conductor spans, from non tangent spans,
or from broken-wire conditions in which the tensions in the conductor
spans become unbalanced.

Under vertical load, the pin acts as a simple column, transmitting
its load to the cross arm at the
shoulders resting on the cross
arm. The stress is equal to the
load divided by the area under
pressure, the area of the shoulder
resting on the cross arm.

This component is usually not
large compared with the other
components acting on the pin
and is often neglected.
Under horizontal loadings,
the pin acts as a cantilever
beam, and the maximum stress
occurs at the point where the pin rests on the arm; refer to Figure 5-10. The
bending moment M is equal to the load P
multiplied by the distance of the conductor
above that point (h):


Double Pins
Double pins, one on each of the double arms, are used where the
strength of one pin is inadequate.

Pins in Lieu of Cross Arms

The advent of wye primary systems employing a common neutral
with the secondary (situated on the pole in the secondary position) allowed
single-phase primary conductors to be supported on a steel ridge
pin, as shown in Figure 5-11. The vertical loading on the pin, the weight
of the ice-coated conductor, is transmitted to the pole through the bolt
by which the pin is attached to the pole. Horizontal loadings, from both
wind and conductor tension, act on the pin as a cantilever beam, and the
same analysis of stresses in the pin, bolt, and pole applies here as with
cross arms.

In polyphase systems, the conductors
may be supported on pins attached
directly to the pole, eliminating the use
of cross arms (this method of support is
sometimes referred to as “armless construction”).

This not only makes for a
neater appearance, but, as indicated earlier,
improves electrical performance by
mitigating the voltage drop due to the reactance
of the line. (The arrangement and
spacing of the conductors accounts for the
lessened reactance. Also, this construction
employs bucket trucks or platforms for
easier access to the conductors.)

In this instance, the vertical loading
acts on the end of the pin, with the pin
acting as a cantilever beam; the bending
stress occurs at the pole, and the fiber
stresses on the pin are calculated in the
same manner described above for cross
arms and poles.

The horizontal loading
acts to create compressive stresses in the pin, which acts as a slender
column. Again, this component is small compared with the other components
and is often neglected. On the other side of the pole, however,
the horizontal forces act to pull the conductor away from the pole; while
there is ample strength for the tensile stress imposed on the pin and the
bolts with which it is attached to the pole, these forces do dictate that the
conductors be so attached to the insulators as to ensure the conductor
will not be separated from the insulator under the stresses imposed.

For higher voltages, additional space requirements may necessitate
longer pins or the installation of insulated conductors (or both). The
pins may be attached to the pole as indicated in Figure 5-12. Here, the
stresses on the pin from both the vertical and horizontal loads impose
bending moments about the bottom of the pin at the pole. The moments
and stresses on the pins and supporting bolts, indicated in Figure 5-12,
are computed in the same fashion as for the cases mentioned above.
For all applications of the pins, a minimum strength of 700 lb per
pin is usually specified in withstanding unbalanced tension in a conductor
supported by the pin.


Read More - Pins

Cross Arms

By :Taufiqullah Neutron (Masteropik)

Cross arms are now almost limited to carrying polyphase circuits in
areas where appearance is not of paramount importance. They are also
used where lines cross each other or make abrupt turns at large angles
to each other. They are used as alley or side arms in which the greater
part of their length extends on one side of the pole to provide adequate
clearances where pole locations may be affected by limited-space rightsof-
way.

Loadings

The cross arm acts as a beam, supported at the point of attachment
to the pole, and must be capable of being subjected to vertical loadings
from the weight of the conductors (encased in ice) and a 225-lb worker
(specified as an additional safety measure). It is also subjected to horizontal
loadings stemming from winds and from tension in the conductors
where the tensions on each side of the pole do not cancel each other;
e.g., where spans or conductors are not the same on each side of the pole,
at dead ends, bends, or offsets in the line, or where consideration is given
to conductor breaking contingencies.


Stresses
The same principles for determining
stresses in beams as were
applied in the case of poles may also
be applied to cross arms.

Bending Moment

The total bending moment M is equal to the sum of all the individual
loads multiplied by their distances from the cross section under
consideration. Ordinarily, the weakest
section should be at the middle of the arm where it is attached to
the pole. At the pin holes, however, the cross section of the cross arm is
reduced and may, under unusual circumstances, be the weakest point in
the cross arm. The determination can easily be made by computing unit
fiber stress at the several points. Like the pole, the cross arm acts as a
beam and the same formula for determining stresses may be employed.

Double Arms
When fiber stresses approach the maximum safe values for a particular
kind of wood (always keeping in mind a factor of safety of 2),
two arms or double arms are used. Ordinarily, these are found at dead
ends, at points where loads are greatly unbalanced (such as large offsets
or bends in the line), and at intermediate points along a long line to limit
damage in the event that conductor breaks create severe load unbalances
on the supporting structures.

The two arms are placed one on each side of the pole and bolted
together near the ends, and often at intermediate points. Properly constructed,
with spacers of wood or steel between the arms, the structure
created would act as a truss with strengths of 10 to 12 times that of a
single arm, or 5 to 6 times that of the two arms considered individually.

Since such quality trusses may not always be constructed in the field,
prudence dictates that only the ultimate fiber strength equivalent to that
of two cross arms be considered. Where the loadings on the arms may
exceed their fiber strengths, the arms may be guyed, as shown in Figure
5-8, or steel arms may be substituted
for wooden ones.

Douglas fir and long leaf yellow pine are the most popular kinds of
wood used for cross arms, though other kinds may also be found in
use. Their ultimate bearing strengths.


Cross-arm Braces
Cross arms fastened to poles
are usually steadied in position by braces. Flat braces, usually flat strips
of galvanized steel bolted to the cross arm and fastened to the pole by a
lag screw, are most commonly used. The support given the cross arm by
the flat braces is questionable, and is usually neglected in determining
the effects of loads on the cross arm. Where the cross arm is not symmetrically
loaded on each side of the pole, the brace on the load side is
in compression and is of little benefit because of its slenderness; the brace
on the other side is in tension and aids in transmitting some of the load
to the pole, but does not reduce the bending moment.

For heavier loads, a preformed brace made of angle iron, of larger
cross section than the flat brace, aids in supporting the loads on the cross
arm. Here, the moments acting on the cross arm are usually computed
about the point of attachment of the angle brace to the cross arm.
For alley or side arms, an angle-iron brace is used; usually it is a
straight length with the ends adapted to be fastened to the arm and the
pole.

The brace transmits a considerable part of the load on the arm to
the pole; when all the load on the arm is beyond the brace, the vertical
compressive stress on the brace may be even greater than the load. The
points of attachment at the cross arm and at the pole are important; the
smaller the angle between the pole and the brace, the greater the load
transmitted to the pole. On the other hand, as the length of the brace
increases, the slenderness ratio (the brace acting as a slender column)
becomes larger and the effectiveness of the brace diminishes.

Bolts

The stability of a cross arm and its strength rely heavily on the
strength of the bolts through which the stresses are transmitted. The
distribution of stresses on the through bolt holding the cross arm to
the pole are shown in Figure 5-9a. The vertical load on the cross arm is
transferred by the bolt to the pole.


Read More - Cross Arms

Poles

By :Taufiqullah Neutron (Masteropik)

Stresses
The forces acting on a pole stem from the vertical loading occasioned
by the weight it has to carry and from the horizontal loadings
applied near the top of the pole. These latter are exerted by the conductors
as a result of uneven spans, of offsets and bends in the lines, and of
the pressure of wind blowing against them. Both vertical and horizontal
loadings include the effects of ice collecting radially about the conductors.

The vertical force on the pole is the dead weight of the conductors
with their coatings of ice, cross arms, insulators, and associated
hardware. This vertical force exerts a compressive stress that may be
considered uniformly distributed over the cross section of the pole. This
loading, however, is almost always overshadowed by the requirements
of the horizontal loadings, and is usually not given further attention.
Even a very light pole can safely carry the dead weight of a multicircuit,
large-conductor line.

Assume relatively long spans of 200 ft, six primary conductors on two
cross arms, and one heavy neutral (for two three-phase feeders) and three secondary
conductors on a rack; moreover, the cross arms are two sets of double
arms, with insulators and associated pins and hardware.
Assume no. 4/0 copper or 397,500-cmil ACSR (250 cmil × 103 copper
equivalent), the largest usual distribution conductor, with a radial half-inch coating
of ice (at 57 lb/ft3).* Assume a light pole, class 5 pine, with a minimum (top)
circumference of 19 in (disregard the effect of the larger, lower cross-sectional
areas because of taper; i.e., assume a cylindrical column).

From wire manufacturers’ tables, no. 4/0 copper wire has a diameter of
0.528 in and a weight of 640.5 lb per 1000 ft; and 397,500-cmil ACSR has a diam
eter of 0.806 in and a weight of 620.6 lb per 1000 ft. The total weight, including
ice, for 200 ft (100 ft on each side of pole) for the copper conductors is 2120 lb
plus 500 lb allowed for four cross arms, insulators, etc., or 2620 lb. For the ACSR
conductors, it is 2840 lb, plus the same 500 lb, or 3340 lb.


Wind Pressure
In arriving at M, if P is the wind pressure on the length of the conductor,
including its coating of ice, and h the distance or height from the
ground at which the circular cross section is to be determined, the total
moment for the several conductors that may be supported is the sum of
the values of Ph for all the conductors.
To this must be added the wind pressure on the pole itself. Here,
the longitudinal cross section of the pole may be broken down into a
rectangle and a triangle, as indicated.


Equipment on Poles
Poles supporting transformers, capacitors, regulators, switches, or
other equipment support loads which are principally compressive in
nature; the equipment also adds to the wind loading. Since the center
of gravity projects out from the pole, a moment is created on the upper
portion of the pole, pivoting about its lower point of support. Ordinarily,
the pole class selected for supporting the conductors, with its factors
of safety included, is capable of carrying this additional load safely. For
larger-scale equipment installations, however, a pole one class greater
than that adequate for the conductors is specified.
Read More - Poles

Criteria

By :Taufiqullah Neutron (Masteropik)

The mechanical design of the distribution system, and its several
parts, must not only be adequate to sustain the normal stresses
and strains, but must safely sustain them during abnormal conditions
brought about by the vagaries of nature and people. While design criteria
for overhead systems are substantially different from those for underground
systems, in both instances prudent design takes into account
economic and other nontechnical considerations.

For overhead systems, the supports for the conductors and equipment
must withstand the forces imposed on them, while the conductors
themselves must be sufficiently strong to support their own weight and
the forces imposed on them.

National Electric Safety Code (NESC)

Minimum design criteria are suggested in the National Electric
Safety Code (NESC) issued by the Institute of Electrical and Electronics
Engineers (IEEE). The NESC has received wide acceptance by utilities
and other industries in this country and elsewhere.

In general, the code specifies:
1. Clearances between conductors and surrounding structures for different
operating voltages and under different local conditions
2. Strength of materials and safety factors used in proposed structures
3. Perhaps the most basic, the probable loading imposed on the conductors
and structures based on climatic conditions, approximately
defined by geographic areas of offsets and bends in the lines, and of
the pressure of wind blowing against them. Both vertical and horizontal
loadings include the effects of ice collecting radially about
the conductors.

The vertical force on the pole is the dead weight of the conductors
with their coatings of ice, cross arms, insulators, and associated
hardware. This vertical force exerts a compressive stress that may be
considered uniformly distributed over the cross section of the pole. This
loading, however, is almost always overshadowed by the requirements
of the horizontal loadings, and is usually not given further attention.
Even a very light pole can safely carry the dead weight of a multicircuit,
large-conductor line.

The NESC divides the country into heavy, medium, and light load
areas. The heavy loading area comprises roughly the northeast quarter
of the “lower 48” states, and Alaska; the medium loading area comprises
the northwest quarter plus a strip across the middle of the country; the
light loading area comprises California and all the southern part of the
country to a depth of some 300 to 400 mi, and Hawaii. The degrees
of loading are indicated in Table 5-1, and the geographic areas for the
continental United States in the map shown in Figure 5-1. The values
and areas of demarcation are approximate and should be subject to
other practical considerations, including probable deviations based on
actual experience, local codes and regulations, and other environmental
requirements.
Read More - Criteria