Tuesday, September 14, 2010

Transformers

By :Taufiqullah Neutron (Masteropik)

Transformers play a central part in the design of distribution systems;
they reduce the high voltage of the primary to the low utilization
voltage of the secondary. As with other elements of the distribution circuit,
the energy losses and the drop in voltage due to the current flowing
through them to supply loads are factors in the selection of the size and
location of transformers.

Losses

Energy losses in a transformer are generally of two kinds:
1. No-load loss (also known as iron or core loss) results from the mag
netizing or exciting current flowing in the primary coil regardless
of the load carried. Its value of about 0.5 percent at rated full load
may vary substantially at voltages above or below rated values.
Although small as a power loss, it goes on constantly, accumulating
into significant annual energy losses (in kilo-watt-hours).

2. Full-load losses (earlier known as copper losses) result from the
load current passing through the resistance of both primary and
secondary coils. This I^R loss varies with the square of the current
carried and therefore depends on the shape of the load curve. Since
the current flowing in a circuit is inversely proportional to the
voltage, the copper loss is inversely proportional to the square of
the voltage; hence, for the same-size transformer, the losses in the
primary coil are substantially less as the voltage ratings increase.
No-load and full-load losses for the various sizes of transformers vary
with different manufacturers and are usually specified by them in some
percentage of normal voltage and full-load ratings. No-load losses may be
expressed in watts or as a percentage of the full rated load in watts.

Impedance—Resistance and Reactance

Copper losses, as well as voltage regulation, require that resistance
and reactance values (and their vector sum, impedance) of the
transformer be known. These three values represent both primary and
secondary coils of the transformer. They are usually specified by the
manufacturer as a percentage related to the percentage voltage drop.
That percentage gives a value in volts when applied to either primary
or secondary voltage; from that voltage and the full rated current the
values in ohms may be derived.

The percentage impedance given for a transformer represents (and
is equivalent to) the percentage drop from normal rated primary voltage
that would occur when full rated load current flows in the secondary;
thus the percentage impedance can be used to determine the impedances
(in ohms) of the primary and secondary as follows.


Voltage Drop
The determination of voltage drop through the transformer employs
values of impedance, resistance, and reactance, as indicated in the
previous discussion of primary and secondary systems. The drop must
be referred to either the primary or the secondary side:
Voltage drop (primary) = Ip(Rp cos θ + X sin θ)
where Ip is the load current and cos θ the power factor.
Voltage drop (secondary) = Is(Rs cos θ + X sin θ)
% voltage drop voltage drop (primary) voltage drop (secondary)
——————— = —————————— = ———————————
100 rated primary voltage rated secondary voltage

These same phase-to-neutral values of Z, R, and X can also be employed
in polyphase circuits. Since phase to phase voltage (for a threephase
circuit) is √3 times the phase-to-neutral value and the voltage
value in the equation is squared, the ratio between phase-to-phase and
phase-to-neutral characteristics is 3 to 1. If the transformer kVA value is
the three-phase total kVA and Ep is the phase-to-phase voltage,

Single-phase
The standard single-phase distribution transformer is generally designed
with the secondary coil in two parts, which may be connected in
parallel for two-wire 120-V operation, or in series for three-wire 120/240
V operation. The latter is the most commonly used connection for singlephase
distribution systems. The load is balanced between two 120-V
circuits; with perfect balance, no current flows in the center or neutral
wire. Refer to Figure 4-6a.

Three-phase

For three-phase systems, the wye-connected secondary can serve
single-phase loads at 120 V for each phase; when the load is balanced,
the neutral will carry no current. This connection can also supply threephase
power loads at 208 V between phases, and it is best adapted for
use on secondary networks. It does have the disadvantage of a lowered
three-phase (208 V) voltage supply to three-phase motors with standard
ratings of 240 V; the 32-V difference, or 13.3 percent, below the rating
may affect the operation of the motors. To remedy the situation, the secondary
voltage is often raised to 125 V, yielding about 217 V between
phases or about only 10 percent less than the standard 240-V rating,
more likely to be within the design tolerances for satisfactory operation.
See Figure 4-6b and c.

The primary supply to this four-wire wye secondary connection
can be either delta- or wye-connected; in the latter case, the wye is usually
grounded to prevent voltage unbalances from unbalanced secondary
loads from distorting phase relationships. Often, further economy is
achieved if both the primary and secondary circuits employ a common
neutral conductor.

Small amounts of three-phase power loads may be supplied on a
chiefly single-phase system by a small-diameter-conductor extension of
another phase and the installation of a small-capacity single-phase transformer
in an open-wye or open-delta bank (on the primary side) with
the principal single-phase transformer.

The secondary of this second
single-phase transformer is connected in an open-delta configuration
with the secondary of the principal transformer, providing a small threephase
delta power supply to the small three-phase requirement. Because
of the phase relationship of the voltage and current, however, only 86
percent of the capacity of this second, small single-phase transformer
can be utilized. This is an economical method of supplying a small,
isolated three-phase load in the midst of an area supplied from singlephase
facilities.

Two-phase

Although two-phase systems are virtually extinct, there are still
some two-phase power loads in existence. These may be supplied from
three-phase delta or wye systems through proper connections of two
single-phase transformers.

Boost-Buck
Earlier, reference was made to the use of single-phase transformers
to boost or buck the line voltage of a primary feeder. Here, the primary
and secondary of the transformer are connected in series, essentially operating
as an autotransformer. The incoming primary coil is connected
across the primary circuit, while the outgoing primary is connected
between a common terminal of the primary of the transformer and the
terminal of the secondary coil; the voltage of the secondary coil is either
added to boost the primary voltage or subtracted to buck it. The capacity
of the secondary coil limits the primary current that may flow through
it.
Three-phase Units

Connections for three-phase transformers and lead markings are
shown in the IEEE classification of polarities.

Autotransformers

Under certain conditions, when the ratio of transformation desired
is low, usually not greater than about 5 to 1, and electrical isolation
between primary and secondary circuits is not essential, the autotransformer
has some advantages.

The autotransformer consists of one winding, a part of which may
serve as both primary and secondary. In a two-winding transformer, all
of the energy is transformed by magnetic action. In the autotransformer,
a portion only is transformed magnetically and the remainder flows
conductively through a part of its windings. Since only a portion of the
energy is transferred, the autotransformer can be smaller than a twowinding
unit; comparable costs of the unit and its installation are less.
Read More - Transformers

Reactors

By :Taufiqullah Neutron (Masteropik)

Primary
Where relatively high-voltage primary feeders (23-kV and above)
operate in metallic sheathed cables and are rather long, the capacitance
effect of the cable may cause undesirable voltage rises along the feeder.
Reactors connected between the primary conductors and the neutral or
ground are inserted in the feeder at appropriate points to hold customer
voltages within permissible limits; shunt reactors act in a similar fashion
as shunt capacitors.

Secondary

Where two or more transformers supply a common load, the transformers
may not share the load equitably. This may be due to differing
secondary voltages at the transformers’ terminals either because the
primary feeder voltages are different, or because the transformers have
different impedances. Reactors inserted in the secondary leads of one or
more of the transformers are installed in an effort to equalize the voltages
and make the transformers share the load equitably.

This phenomenon is often evident in low-voltage secondary networks, and especially
in “spot networks.” In this latter case, the terminals of the reactor coil of
one transformer are interconnected to those of another transformer with
the leads reversed. Hence, the voltage drop in each of the reactances is
added to or subtracted from the several secondary voltages, tending to
balance the load among the several supply transformers.
Read More - Reactors

Friday, September 10, 2010

Capacitors

By :Taufiqullah Neutron (Masteropik)

Voltage regulation can also be improved by the application of
shunt capacitors at the substation, out on the primary feeder, or both.
The current drawn by a capacitor has a leading power factor characteristic
and will cause a voltage rise from the location of the capacitor back to
the current source.

The voltage rise will be equal to the reactance of the
circuit (back to the source) multiplied by the capacitor current (taking
into account their vector relationship). The rise in voltage is independent
of the load on the circuit and is greatest at the location of the capacitors
and decreases to the source.

Capacitors provide a constant increase in the level of voltage at the
location of the capacitor that is the same under any load condition of
the feeder, from light to heavy loading. If capacitors are installed so that
they may be switched on during heavy load periods and off at light load
periods, voltage regulation can be improved. If a bank of capacitors is
so arranged that some of its units can be switched on and off separately,
voltage regulation can be improved even further.

Primary Feeder

When they are installed out on a primary feeder, the capacity of
the capacitors (in kVA) and the location on the feeder where they are
to be installed depends on the manner in which the loads are distributed
on the feeder, the power factor of the loads, the feeder conductor
size and spacing between conductors, and the voltage conditions
along the feeder.

Like the line voltage regulator, capacitors should be
installed approximately at the point where the voltage at heavy load
is at the minimum permissible level (with some consideration given
to load growth). The conditions under light load will determine what
portion of the capacitance installed may be fixed and what may be
switched.

Substations
Capacitors may also be installed at substations on the bus supplying
the outgoing distribution feeders. They are usually installed in
relatively large-capacity banks, and it is usually necessary to switch off
portions of them at periods of light load to prevent excessively high
outgoing voltage


The voltage drops along the feeders supplied from
this substation bus remain the same as do their power factors, since the
relationship between the voltage and current flowing through each of
the feeders supplying their loads is unaffected by the capacitors added
to the substation bus. The voltage level of each of the entire feeders is
raised depending on the capacitance added at the substation, but the
voltage spread on each feeder remains the same.

In many instances, the principal reason for the capacitors at the substation bus is not necessarily
to control the bus voltage, but, by counteracting the effect of induction
(or reactance), to reduce the current to that necessary to supply the load
at approximately unity power factor, thereby permitting larger loads to
be supplied by the same transmission and substation facilities.

Series Capacitors

Capacitors can also be installed in series with primary feeders to
reduce voltage drop, but they are rarely employed in this fashion. Where
shunt capacitors, connected in parallel with the load, correct the component
of the current due to the inductive reactance of the circuit, series
capacitors compensate for the reactive voltage drop in the feeder.

A capacitor in series in a primary feeder serving a lagging-power
factor load will cause a rise in voltage as the load increases. The power
factor of the load through the series capacitor and feeder must be lagging
if the voltage drop is to decrease appreciably. The voltage on the
load side of the series capacitor is raised above the source side, acting
to improve the voltage regulation of the feeder. Since the voltage rise
or drop is produced instantaneously with the variations in the load, the
series capacitor response as a voltage regulator is faster and smoother
than the induction or TCUL-type regulator; moreover, no contact-making
voltmeter and load compensator are required for its operation.

During fault conditions, however, the large fault current passing
through the series capacitor can develop excessive voltage across the
capacitor, sufficient to cause its destruction. It is essential, therefore,
that it be taken out of service as quickly as possible. A resistor and
air gap are connected between the terminals of the series capacitor.
When the voltage becomes sufficiently high, the gap breaks down and
permits the capacitor to be short-circuited through the resistor; the
resistor dampens out any oscillatory discharge current so the gap can
break down and restrike repetitively without damaging the capacitor.
Auxiliary relays operate to short-circuit and bypass the capacitor if the
fault persists.

Because of the potential hazard, series capacitors as voltage regulators
are usually restricted to supplying single large consumers where
flicker may result from frequent motor starts or from electric welders,
furnaces, and similar devices that may cause rapid and repetitive load
fluctuations.
Read More - Capacitors

Boosters

By :Taufiqullah Neutron (Masteropik)

An increase or decrease in the primary voltage can also be obtained
by the installation of a transformer in the line to provide a fixed voltage
drop. A distribution transformer, connected as an autotransformer, may
be used to boost or buck the feeder voltage at the point of its installation.

The percentage of boost or buck will depend on the ratio of the primary
and secondary coils, including the tap used, of the transformer selected.
The capacity of the unit is determined by the current-carrying capacity
of the secondary coil, through which the entire line current will flow.
(Refer to Figure 4-6k.)

The use of a distribution of normal design in this way is usually
done in an emergency. It is an unsafe method, as the secondary is
connected directly to the primary. For safety reasons, special attention
should be given when connecting or disconnecting such units.
Read More - Boosters
back to top